Range | 100KVA to 10000KVA |
Voltage Class | Up to 33KV Class |
Winding Material | Copper or Aluminium |
Cooling | ONAN/ONAF |
Type (Duty) | Outdoor / Indoor |
Vector Group | Dyn1/ Dyn5 / Dyn11 or as per specific requirement |
No. of Phase | 3 Phase |
Tap Changer | Off Circuit or On Load Tap Changer |
Insulating Oil/Fluid | Mineral Oil / Silicon Oil / Ester Oil |
Applicable Standards | IS 2026, IS 1180, IEC 60076 |
Cement Industries | Steel Industries | Chemical Industries | Solar Applications (Renewable Energy) | Refineries | Electricity Boards | Infrastructure | Utilities | Railways & Metro | Power Plants
Range | 100KVA to 10000KVA |
Voltage Class | Up to 33KV Class |
Winding Material | Copper or Aluminium |
Cooling | ONAN/ONAF |
Type (Duty) | Outdoor / Indoor |
Vector Group | Dd0yn11 / Dyn11-yn11 or as per specific requiremen |
No. of Phase | 3 Phase |
Tap Changer | Off Circuit or On Load Tap Changer |
Insulating Oil/Fluid | Mineral Oil / Silicon Oil / Ester Oil |
Applicable Standards | IS 2026, IS 1180, IEC 60076 |
Cement Industries | Steel Industries | Chemical Industries | Solar Applications (Renewable Energy) | Refineries | Electricity Boards | Infrastructure | Utilities | Railways & Metro | Power Plants
Induction Furnace has a coil constructed from heavy copper tubing. It is designed and tuned to the inverter circuit which applies a medium frequency (generally 500 Hz or 1000 Hz) voltage to the Induction coil. The magnetic field produced by the induction coil induces eddy currents in the charge and heats it. Medium frequency is necessary to enhance the rate of heat generation.
Range | 100KVA to 10000KVA |
Voltage Class | Up to 33KV Class |
Winding Material | Copper |
Cooling | ONAN/OFWF |
Type (Duty) | Outdoor / Indoor |
No. of Phase | 3 Phase |
Tap Changer | Off Circuit or On Load Tap Changer |
Insulating Oil/Fluid | Mineral Oil / Silicon Oil / Ester Oil |
Applicable Standards | IS 2026, IS 12977 |
Rolling Mills | Steel Plants | Metal Industries
Range | For system Up to 33KV Class |
Winding Material | Copper |
Vector Group | ZN0/ZNYN1/ZNYN11 |
Tap Changer | Off Circuit |
Applicable Standards | IS 2026, IS 1180, IEC 60076 |
Industrial Sectors | EHV Substations
Sr No. | Rating (kVA) | Impedance (Percent) | Maximum Total Loss (W) | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Energy Effciency Level 1 |
Energy Effciency Level 2 |
Energy Effciency Level 3 |
Energy Effciency Level 4 |
Energy Effciency Level 5 |
||||||||
50 Precent Load |
100 Precent Load |
50 Precent Load |
100 Precent Load |
50 Precent Load |
100 Precent Load |
50 Precent Load |
100 Precent Load |
50 Precent Load |
100 Precent Load |
|||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
i) | 250 | 4.50 | 980 | 2930 | 920 | 2700 | 864 | 2488 | 811 | 2293 | 764 | 2113 |
ii) | 315 | 4.50 | 1025 | 3100 | 955 | 2750 | 890 | 2440 | 829 | 2164 | 772 | 1920 |
iii) | 400 | 4.50 | 1225 | 3450 | 1150 | 3330 | 1080 | 3214 | 1013 | 3102 | 951 | 2994 |
iv) | 500 | 4.50 | 1510 | 4300 | 1430 | 4100 | 1354 | 3909 | 1282 | 3727 | 1215 | 3554 |
v) | 630 | 4.50 | 1860 | 5300 | 1745 | 4850 | 1637 | 4438 | 1536 | 4061 | 1441 | 3717 |
vi) | 800 | 5.00 | 2287 | 6403 | 2147 | 5838 | 2015 | 5323 | 1892 | 4853 | 1776 | 4425 |
vii) | 1000 | 5.00 | 2790 | 7700 | 2620 | 7000 | 2460 | 6364 | 2310 | 5785 | 2170 | 5259 |
viii) | 1250 | 5.00 | 3300 | 9200 | 3220 | 8400 | 3142 | 7670 | 3066 | 7003 | 2991 | 6394 |
ix) | 1600 | 6.25 | 4200 | 11800 | 3970 | 11300 | 3753 | 10821 | 3547 | 10363 | 3353 | 9924 |
x) | 2000 | 6.25 | 5050 | 15000 | 4790 | 14100 | 4343 | 13254 | 4309 | 12459 | 4088 | 11711 |
xi) | 2500 | 6.25 | 6150 | 18500 | 5900 | 17500 | 5660 | 16554 | 5430 | 15659 | 5209 | 14813 |